Closed Loop Liquid Cooling of High Powered CPUs
Abstract
This case study presents an experimental investigation of closed loop liquid cooling of CPUs. The cooling system implements a pumped liquid supplying a cold plate fixed to the emulated CPU heat source and a remote Air-Cooled Heat Exchanger (ACHE). The Hybrid Liquid-Air (HLA) system employs 25% v/v Arteco-Freecor with distilled water solution as the primary coolant, and air as the secondary coolant. The thermal-hydraulic performance of the system is characterized over a range of operating conditions, including CPU heat loads (12 W/cm2 – 72 W/cm2), water volumetric flow rates (0.5 L/min – 8 L/min), and air velocities (1m/s – 3m/s). In order to provide a performance frame of reference, evaluations were also conducted with a conventional air-based fan- fin CPU cooling system.

…The results indicate that the HLA system significantly outperforms the traditional air-cooled fan-fin system, with much lower CPU temperatures and feasible power levels exceeding 300 W.
Copyright © 2024 Nexalus Ltd. All rights reserved.
References:
a. Department of Mechanical and Manufacturing Engineering, Parsons Building, Trinity College Dublin, D2, Ireland
b. Nexalus Labs, Water St, Loughanalla, Castlepollard, Co Westmeath, Ireland
c. CONNECT, Dunlop Oriel House, Trinity College Dublin, Ireland.
F.M. Naduvilakath-Mohammeda,b,c, R. Jenkinsb, G. Byrnea, A.J. Robinsona,b,c
Featured
Posts
Nexalus and Tracewell Systems Partner to Advance Next-Generation Edge AI Infrastructure Solutions for U.S. Civilian and Military Agencies
Knowledge HubNexalus Partners With TuffTek to Bring Liquid Cooling to Rugged Military Computing
Knowledge HubCork’s Nexalus teams with TuffTek for next-gen cooling systems
Knowledge HubNexalus and TuffTek Announce Strategic Collaboration to Deliver Advanced Liquid Cooling Solutions for Defence and Edge Applications
Knowledge HubNexalus Selects Alps Alpine as Global Manufacturing Partner for Next Generation Thermal Management in Digital Infrastructure
Knowledge HubWhat Porsche’s shift from air to water cooling teaches us about thermal management in data centers
Knowledge Hub